Gas Alarm Controller
Gas Alarm Controller

Product Overview:

Product overview: AGP2100 gas alarm controller is suitable for the control and communication of standard 4-20mA current signals and bus RS485 signals. The controller system adopts advanced high-precision single-chip processing technology. Strong.FIX2100 gas alarm controller is connected to a gas detector to continuously monitor the dangerous gas in the environment, display the concentration of the measured gas according to the received input signal, and communicate with the host computer through RS-485 digital signal.Alarm records can be queried and stored, and external equipment can be controlled through relay output, such as exhaust system or other external equipment.

Parameters: 2 public relay outputs (failure alarm, primary and secondary alarm), 8 programmable relay outputs;
Parameters: Alarm parameter setting, shielding setting, system time setting, communication parameter setting can be set through the touch screen, the current signal can be calibrated, and the alarm sound can also be silenced
Parameters: Provide RS232 or RS485 and Ethernet communication interface for communication with PLC or computer;
Parameters: The alarm records and data records in the TF memory card (optional) can be exported through USB;
Parameters: Through the operating system menu on the touch screen, the main display screen of the inspection will display the measured gas concentration value, alarm information, fault information, shielding information, storage information, installation location and other information;
Product characteristics and parameters ▼

main feature:

g) Configurable backup power supply (optional), the main power and backup power are automatically switched and the backup power working status icon is displayed intuitively in the menu bar;

h) The alarm channel number, alarm status and alarm time can be directly queried through the menu;

i) The short-distance RTU wireless transmission method or the unlimited-distance GPRS wireless transmission method can transmit real-time detection data and alarm status to the safety center through the built-in wireless module (optional); 

The main function:

Alarm function

When the following situations occur, the controller will send out an audible and visual alarm signal:

a) When the measured gas concentration exceeds the set first-level (A1 low alarm) alarm value or second-level (A2 high alarm) alarm value, the buzzer will make continuous beeps, the concentration alarm indicator light is on, and the public relay is activated. combine;

b) When the controller is connected to the gas detector circuit and there is a failure, such as: no signal output, transmission line disconnection, transmission line short circuit, gas detector signal output exceeds the measurement range, the buzzer will beep continuously, and the fault alarm will be issued at the same time The indicator light is on, and the public relay is closed;

c) When the main power is cut off and the controller is powered by the backup power, the buzzer will beep briefly, and when the voltage of the backup power is insufficient, the buzzer will beep continuously.

Self-test function

Self-inspection when starting up, the controller automatically checks the functions of the indicator lights and buzzers on its panel. The instrument self-test menu can also perform functional self-test on the status indicator, buzzer and relay.

Data logging function

Through the menu, you can directly query historical data records and real-time curves, and you can customize the data saving interval. When the gas concentration of a certain channel exceeds the set alarm value, the alarm channel number, alarm concentration value and alarm time will be automatically recorded.

Parameter setting function

The working parameters of the controller can be viewed and modified at any time, including the current date/time, measurement range, resolution, alarm values at all levels, channel shielding, installation location, etc.


Main and backup power automatic switching function

When the main power supply of the controller is cut off, it can automatically switch to the backup power supply; when the main power supply is restored, it can automatically switch to the main power supply; the working status of the main and backup power supplies is indicated by an indicator light. When the main power supply is working, it can charge the backup power supply at the same time, and it will automatically turn to the floating charge state after the backup power is fully charged.

Alarm output control function

The controller has 2 public alarm output relays and 8 programmable alarm output relays. Equipment for controlling fire-fighting equipment, ventilation equipment, alarm equipment or other purposes. .

Current Calibration Function

The controller can calibrate the input current signals of 4mA, 12mA and 20mA to ensure timely synchronization of signals.

communication function

The controller has 3 RS-485 ports and 1 Ethernet port, which can easily transmit data to other control devices, computers, etc. The default address of the controller is: 5, and the baud rate is: 9600.
Other functions

Display of the total number of alarm channels, 4~20mA current signal output, etc.

Product parameters:

product name

Gas Alarm Controller

Product number

AGP2100

Working power

220VAC +10%, -15%; 50Hz ±5Hz

fuse

Rated current: 10A Size: 5mm*20mm

Maximum operating current

1.5A (24VDC)

backup power

14.8VDC, 5.2AH (polymer lithium battery)

output power

24VDC, 1000mA

Way of working

Inspection

input signal

① 4~20mA current signal (three-wire gas detector)
② Bus RS485 signal optional (standard MODBUS protocol).

control channel

① 4~20mA current signal split line type: support 1 channel to 32 channels
② Bus system RS485 signal: support 1-255 points

output signal

4~20mA current signal (optional)

alarm record

Alarm location display, alarm event record, time, concentration, etc.

Alarm value setting

A1 alarm value, A2 alarm value; interval alarm

Alarm function

LED indicator light and buzzer sound alarm

Alarm Output

2-way public relay output, 8-way programmable relay output

Contact rating

220VAC, 1A

Communication Interface

RS-485 MODBUS; 3 RS-485 ports and 1 Ethernet port

Operating temperature

-20°C - 55°C

Working humidity

0-95% relative humidity (non-condensing)

Environmental pressure

86~106kPa

Display method

7-inch or 9-inch touch TFT-LCD color LCD screen, 800x480 dot matrix LCD

measurement accuracy

≤±1% (current signal)

shell material

SPCC (optional 304 or 316 stainless steel)

Dimensions

Length 300mm x height 400mm x width 100mm

weight

about 6.5kg

Alarm method

Sound alarm 95 dB@30cm, red LED concentration indicator light, short-distance wireless and unlimited distance GPRS wireless alarm transmission mode

button

Touch operation, with the three-key operation of mute, lock screen, and flip screen

direct reading

Measured value, ambient temperature, humidity

data record

Automatic storage, can store 300,000 sets of data with date and time continuously, optional TF memory card, can store more than 10 million sets of data

data download

Support USB measurement data download;

data transmission

Support RTU wireless transmission or unlimited distance GPRS wireless transmission (optional)

data printing

Support micro data printer serial port printing

calibration

Support 4mA, 12mA, 20mA three-level current calibration operation

degree of protection

IP54

operating mode

Two operating modes, user mode and administrator mode, are available

Executive standard

GB16808-2008